POST ABATEMENT AIR CLEARANCE – NIOSH 7400 Protocol
The photo is an example of what not to do for clearance.
This risk is still dirty post abatement.
Silica is every where.
Another clearance is needed.
AHERA Final Clearance Protocol with NIOSH 7400 PCM Method & TEM if needed.
✔ Containment area must be up & visually clean (no dust, debris, or visible residues).
✔ All surfaces should have been HEPA vacuumed & wet wiped.
✔ Negative air machines (NAMs) should be running during testing.
✔ No entry – clearance sampling personnel.
3.1. Agitate the Air Using a Leaf Blower – Gas or Electric
• Inside the containment area, blow at all surfaces, ceilings, & walls to disturb settled fibers.
• Focus on where fibers may have settled.
• Blow air throughout the room for 5 minutes per 1,000sf.
3.2. Use a Box Fan to Maintain Air Suspension
• After leaf blower agitation, place a box fan in the center of the room.
• Set the fan on high speed to maintain air turbulence.
• Run fan run for at least 5 minutes before air sampling.
4. Conduct Clearance Air Sampling (AHERA/NIOSH 7400 Method)
✔ Minimum 5 air samples inside the containment area (per AHERA).
✔ Place samplers at breathing zone height (4-6 feet from the floor).
✔ Keep samplers at least 3 feet away from walls and corners.
4.2. Calibrate Air Sampling Pumps
• Attach clean MCE filters (0.8 μm pore size) to high-volume air pumps.
• Set pumps to 10–15 L/min flow rate.
4.3. Start Air Sampling
• Run the pumps for at least 4 hours, or until a total of 1,200 liters of air is sampled per cassette.
• Monitor pumps every hour to ensure proper function.
5.1. Fill Out Chain of Custody (COC) Form
• Date, time, and duration of sampling
• Flow rate used (L/min)
• Analysis method requested (PCM or TEM)
• Submit to an NVLAP-accredited laboratory.
5.2. Analysis Method
• Primary analysis: PCM (NIOSH 7400)
• If PCM results exceed 0.01 fibers/cc, then TEM (AHERA method) must be used for confirmation.
6. Clearance Criteria (Pass/Fail Standards)
• PCM (NIOSH 7400): Pass if <0.01 fibers/cc
• TEM (EPA AHERA Method): Pass if:
• <70 structures per mm² of filter
If fiber levels exceed 0.01 fibers/cc, it fails clearance:
1️⃣ Re-clean containment area (HEPA vacuum & wet wipe all surfaces).
2️⃣ Repeat air agitation process with the leaf blower and fan.
3️⃣ Conduct a second round of clearance air sampling.
4️⃣ If levels still fail, submit samples for TEM analysis to determine if the fibers are asbestos or non-asbestos.
Field Summary of Steps
✔ Always use a leaf blower & fan for aggressive air clearance (AHERA requires it).
✔ Ensure all surfaces are HEPA vacuumed & wet wiped before sampling.
✔ Sample at least 1,200 liters of air per filter for accurate results.
✔ Submit outdoorsamples for TEM comparison if PCM fails.
✔ Retain all field records, chain of custody, and pump calibration logs for compliance.